Panasonic FP-E Programming Manual page 1118

Fp series
Table of Contents

Advertisement

FP-e
No.
Pulse catch input
402
settings
Inter-
rupt-
input
Interrupt input
403
settings
Note1) If the operation mode is set to two-phase, incremental/decremental, or incremental/decremental
control, the setting for CH1 is invalid in part 2 of system register 400 and the setting for CH3 is
invalid in part 2 of system register 401.
Note2) If reset input settings overlap, the CH1 setting takes precedence in system register 400 and the
CH3 setting takes precedence in system register 401.
Note3) The settings for pulse catch and interrupt input can only be specified in system registers 402 and
403.
Note4) If system register 400 to 403 have been set simultaneously for the same input relay, the following
precedence order is effective:
1. High-speed counter
2. Pulse catch
3. Interrupt input.
This means, the counter keeps counting even after an interrupt.
5-30
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Default
Name
value
Not set
Not set
Descriptions
Specify the input contacts used as pulse catch
input.
Specify the input contacts used as intrrupt
input.
Specify the effective interrupt edge.
(When set: ON→OFF is valid)