Panasonic FP-E Programming Manual page 1011

Fp series
Table of Contents

Advertisement

F348
(FBAND)
P348
(PFBAND)
Outline
This instruction carries out dead-band control for real number data.
Program example
Trigger
R0
10
F348 FBAND, DT10, DT20, DT30, DT40
S1
S2
S3
D
Operands
Relay
Operand
Operand
WX WY WR WL
S1
A
A
S2
A
A
S3
A
A
D
N/A
A
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Floating point real number data deadband control
Ladder Diagram
Ladder Diagram
S1
S2
The area where the lower limit is stored or the lower limit data. (2 words)
The area where the upper limit is stored or the upper limit data. (2 words)
The area where the input value is stored or the input value data. (2 words)
The area where the output value is stored. (2 words)
Timer/Counter
SV
EV
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
S3
D
Index
Register
register
DT
LD
FL
I
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
* Index modification of a real number is not possible.
High−level Instructions
Boolean
Address
Instruction
10
ST
R
11
F348(FBAND)
DT
DT
DT
DT
Constant
Index
modifier
modifier device
K
H
f
A
A
A
A*
A
A
A
A*
A
A
A
A*
N/A N/A N/A
A
A:
Available
N/A: Not Available
0
10
20
30
40
Integer
device
A
A
A
A
3 − 747