Mitsubishi Electric MELSEC-L LD75P User Manual page 89

Positioning module
Hide thumbs Also See for MELSEC-L LD75P:
Table of Contents

Advertisement

(10)For compliance with the EMC and Low Voltage Directives, satisfy the following
requirements.
The cable connecting the drive unit and the LD75 must be the length below.
• LD75P: 2m or shorter
• LD75P: 10m or shorter
Use shielded twisted pair cables and an AD75CK type cable clamp (manufactured by Mitsubishi Electric) to
ground the cables to the control box.
Even when compliance with the EMC Directive is not required, attaching an AD75CK type cable clamp to the
cable connected to the LD75 may reduce the influence of external noise.
AD75CK
For details on AD75CK, refer to the following.
 AD75CK-type Cable Clamping Instruction Manual
CHAPTER 4 INSTALLATION, WIRING, AND MAINTENANCE OF PRODUCT
Inside control box
20 to 30cm
4
87

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-l ld75d

Table of Contents