Mitsubishi Electric MELSEC-L LD75P User Manual page 491

Positioning module
Hide thumbs Also See for MELSEC-L LD75P:
Table of Contents

Advertisement

(2) When both the "Forward run JOG start signal" and "Reverse run JOG start
signal" are turned ON simultaneously for one axis
When both the "Forward run JOG start signal" and "Reverse run JOG start signal" are turned ON simultaneously
for one axis, the "Forward run JOG start signal" is given priority. In this case, the "Reverse run JOG start signal"
is validated when the LD75 BUSY signal is turned OFF. If the forward run JOG operation is stopped due to stop
or axis error by a stop signal, the reverse run JOG operation will not be executed even if the "Reverse run JOG
start signal" turns ON.
Forward run JOG start signal
[Y8, YA, YC, YE]
Reverse run JOG start signal
[Y9, YB, YD, YF]
BUSY signal[XC, XD, XE, XF]
Forward run JOG operation
ON
OFF
ON
OFF
The reverse run JOG
start signal is ignored.
ON
OFF
CHAPTER 11 MANUAL CONTROL
t
Reverse run JOG operation
11
489

Advertisement