Mitsubishi Electric MELSEC-L LD75P User Manual page 219

Positioning module
Hide thumbs Also See for MELSEC-L LD75P:
Table of Contents

Advertisement

(9) [Cd.11] New deceleration time value
Item
• When changing the deceleration time during a speed change, use this data item to specify a new deceleration time.
Setting details
• [Cd.11] setting range (unit): 0 to 8388608 (ms)
■Set with a decimal.
Setting
value
Setting value
Example: When the " Cd.11 New deceleration
Default value
0
Axis 1: 1510, 1511
Storage buffer memory
Axis 2: 1610, 1611
address
Axis 3: 1710, 1711
Axis 4: 1810, 1811
(10)[Cd.12] Acceleration/deceleration time change during speed change,
enable/disable selection
Item
Setting details
Enables or disables modifications to the acceleration/deceleration time during a speed change.
■Set with a decimal.
Setting
value
Setting value
Default value
0
Axis 1: 1512
Storage buffer memory
Axis 2: 1612
address
Axis 3: 1712
Axis 4: 1812
Cd.11 New deceleration time value
time value" is set as "60000 ms",
the buffer memory stores "60000".
K
Acceleration/deceleration time change during speed change, enable/disable selection
1: Enables modifications to acceleration/deceleration time
Other than 1: Disables modifications to acceleration/deceleration time
CHAPTER 5 DATA USED FOR POSITIONING CONTROL
Description
Description
5
217

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-l ld75d

Table of Contents