Classification
Error
of errors
code
JOG deceleration time
958
selection setting error
Acceleration/deceleration
959
process selection setting
error
Parameter
960
S-curve ratio setting error
Illegal sudden stop
961
deceleration time
Stop group 1 sudden stop
962
selection error
672
Error name
Operation status at error occurrence
■Description
The set value of the detailed parameter 2 "JOG
deceleration time selection setting" is outside the
setting range.
■Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■Description
The set value of the detailed parameter 2
"Acceleration/deceleration process selection
setting" is outside the setting range.
■Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■Description
The set value of the detailed parameter 2 "S-curve
ratio" is outside the setting range.
■Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■Description
The set value of the detailed parameter 2 "Sudden
stop deceleration time" is outside the setting range.
■Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■Description
The set value of the detailed parameter 2 "Stop
group 1 sudden stop selection" is outside the
setting range.
■Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
Action/Related buffer memory address/Set
range (Setting with program)
■Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■Buffer memory address
Axis 1: 51
Axis 2: 201
Axis 3: 351
Axis 4: 501
■Setting range
0, 1, 2, 3
■Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■Buffer memory address
Axis 1: 52
Axis 2: 202
Axis 3: 352
Axis 4: 502
■Setting range
0, 1
■Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■Buffer memory address
Axis 1: 53
Axis 2: 203
Axis 3: 353
Axis 4: 503
■Setting range
1 to 100
■Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■Buffer memory address
Axis 1: 54, 55
Axis 2: 204, 205
Axis 3: 354, 355
Axis 4: 504, 505
■Setting range
1 to 8388608
■Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■Buffer memory address
Axis 1: 56
Axis 2: 206
Axis 3: 356
Axis 4: 506
■Setting range
0, 1