(4) Setting the skip function using an external command signal
The skip function can also be executed using an "external command signal".
The following shows the settings and program example for skipping the control being executed in axis 1 using an
"external command signal".
1.
Set the following data to execute the skip function using an external command signal.
(The setting is carried out using the program shown below in section 2.).
Setting item
External command
[Pr.42]
function selection
External command
[Cd.8]
valid
Refer to  Page 211, Section 5.7 for the information on detail settings.
2.
Add the following program to the control program, and write it to the CPU module.
Example
Skip function
selection command
Setting value
3
Set "3: Skip request".
1
Set "1: Validate external command".
Input external command signal
CHAPTER 12 CONTROL SUB FUNCTIONS
Setting details
TOP
H0
K62
K3
K1
Skip request
TOP
H0
K1505
K1
K1
External command valid
Buffer memory address
Axis 1
Axis 2
Axis 3
Axis 4
62
212
362
512
1505
1605
1705
1805
<Select skip request>
<Set external command valid>
579
12