(3) Relation between the software stroke limit function and various controls
: Check valid, : Limited during speed control
not carried out
Machine OPR control
OPR control
Fast OPR control
Position
control
Major positioning
1- to 4-axis speed control
control
Speed-position switching control, Position-speed switching
control
Other control
JOG operation, inching operation
Manual control
Manual Pulse Generator Operation
*1
Check is not made when the current feed value is not updated ( Page 132, Section 5.2.3 (11)) at the setting of
"current feed value" in "[Pr.14] Software stroke limit selection" during speed control.
*2
Valid only when "1:valid" is set in the "[Pr.15] Software stroke limit valid/invalid setting".
*3
The value in "[Md.20] Current feed value" will differ according to the "[Pr.21] Current feed value during speed control"
setting.
*4
When the unit is "degree", check is not made during speed control.
*5
When the unit is "degree", check is not carried out.
Control type
1-axis linear control
2- to 4-axis linear interpolation control
1-axis fixed-feed control
2- to 4-axis fixed-feed control (interpolation)
2-axis circular interpolation control
3-axis helical interpolation control
Current value changing
JUMP instruction, NOP instruction, LOOP to
LEND
CHAPTER 12 CONTROL SUB FUNCTIONS
*1
, : Valid only when a certain setting is configured
Limit check
Check not carried out.
Checks 1) and 2) in Page 536, Section 12.4.3
(2) are carried out.
For speed control: The axis decelerates to a
stop when it exceeds the software stroke limit
range.
For position control: The axis comes to an
immediate stop when it exceeds the software
*3*4
stroke limit range.
*3*4
The current value will not be changed if the
new current value is outside the software
stroke limit range.
Check not carried out.
*5
Check 1) in Page 536, Section 12.4.3 (2) is
carried out.
The machine will carry out a deceleration stop
when the software stroke limit range is
*5
exceeded. If the address falls out of the
software stroke limit range, the operation can
be started only toward the movable range.
*2
, : Check
Processing at check
537
12