Classification
Error
Error name
of errors
code
Command in-position
925
width
Illegal torque limit setting
926
value
927
M code ON timing error
Parameter
Speed changeover mode
928
error
Interpolation speed
929
designation method error
Current value update
930
request error
Operation status at error occurrence
■Description
The set value of the detailed parameter 1
"Command in-position width" is outside the setting
range.
■Operation status at error occurrence
The LD75 READY signal (X0) does not turns ON.
■Description
The set value of the detailed parameter 1 "Torque
limit setting value" is outside the setting range.
■Operation status at error occurrence
The LD75 READY signal (X0) does not turns ON.
■Description
The set value of the detailed parameter 1 "M code
ON signal output timing" is outside the setting
range.
■Operation status at error occurrence
The LD75 READY signal (X0) does not turns ON.
■Description
The set value of the detailed parameter 1 "Speed
changeover mode" is outside the setting range.
■Operation status at error occurrence
The LD75 READY signal (X0) does not turns ON.
■Description
The set value of the detailed parameter 1
"Interpolation speed designation method" is outside
the setting range.
■Operation status at error occurrence
The LD75 READY signal (X0) does not turns ON.
■Description
The set value of the detailed parameter 1 "Current
feed value during speed control" is outside the
setting range.
■Operation status at error occurrence
The LD75 READY signal (X0) does not turns ON.
CHAPTER 15 TROUBLESHOOTING
Action/Related buffer memory address/Set
range (Setting with program)
■Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■Buffer memory address
Axis 1: 24, 25
Axis 2: 174, 175
Axis 3: 324, 325
Axis 4: 474, 475
■Setting range
1 to 2147483647
■Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■Buffer memory address
Axis 1: 26
Axis 2: 176
Axis 3: 326
Axis 4: 476
■Setting range
1 to 500
■Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■Buffer memory address
Axis 1: 27
Axis 2: 177
Axis 3: 327
Axis 4: 477
■Setting range
0, 1
■Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■Buffer memory address
Axis 1: 28
Axis 2: 178
Axis 3: 328
Axis 4: 478
■Setting range
0, 1
■Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■Buffer memory address
Axis 1: 29
Axis 2: 179
Axis 3: 329
Axis 4: 479
■Setting range
0, 1
■Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■Buffer memory address
Axis 1: 30
Axis 2: 180
Axis 3: 330
Axis 4: 480
■Setting range
0, 1, 2
15