(25)[Cd.27] Target position change value (new address)
Item
When changing the target position during a positioning operation, use this data item to specify a new positioning address. (
Setting details
Page 227, Section 5.7.2 (25) (a))
■Set with a decimal.
Actual value
Setting value
Setting value
(Decimal)
Example: If " Cd. 27 Target position change
Default value
0
Axis 1: 1534, 1535
Storage buffer memory
Axis 2: 1634, 1635
address
Axis 3: 1734, 1735
Axis 4: 1834, 1835
(a) Setting range
[Pr.1] Unit setting
0: mm
1: inch
2: degree
3: pulse
Cd. 27 Target position change value (address)
Conversion into an integer value
n
× 10
R
value (address)" is set as
"100000.0µm", the buffer memory
stores "1000000".
■ABS, INC
-2147483648 to +2147483647 (10
■ABS, INC
-2147483648 to +2147483647 (10
■ABS
0 to 35999999 (10
■INC
-2147483648 to +2147483647 (10
■ABS, INC
-2147483648 to +2147483647 (pulse)
CHAPTER 5 DATA USED FOR POSITIONING CONTROL
Description
Unit conversion table ( Cd.27 )
n
Unit
m
-1
inch
-5
degree
-5
pulse
0
Setting range
-1
m)
-5
inch)
-5
degree)
-5
degree)
5
227