(2) Restrictions
• Always limit the servomotor torque after the "[Pr.47] Creep speed" is reached. If the torque is not limited, the
servomotor may fail when the machine presses against the stopper. (For details, refer to Torque limit function
( Page 532, Section 12.4.2).)
• Use an external input signal as the zero signal.
(3) Precautions during operation
• Input a zero signal from an external source after the machine presses against the stopper. The workpiece
will continue decelerating and stop if a zero signal is input before deceleration to the "[Pr.47] Creep speed".
An error "OP detection timing fault (error code: 204)" will occur after the machine stops.