(3) Current value changing procedure
The following shows the procedure for changing the current value to a new value.
(4) Setting method for the current value changing function
The following shows an example of a program and data setting to change the current value to a new value with
the positioning start signal. (The "[Md.20] Current feed value is changed to "5000.0m" in the example shown.)
(a) Set the following data.
(Use the start time chart shown in section (b) below as a reference, and set data using the program shown in
section (c).)
Setting item
[Cd.3]
Positioning start No.
[Cd.9]
Current value changing
Refer to  Page 211, Section 5.7 for information on the setting details.
(b) The following shows a start time chart.
[Y10]
Positioning start signal
[Y0]
PLC READY signal
[X0]
LD75 READY signal
[X10]
Start complete signal
[XC]
BUSY signal
Positioning complete signal
[X14]
[X8]
Error detection signal
1)
Write the current value to " Cd. 9 Current value changing"
2)
Write "9003" in " Cd. 3 Positioning start No."
Turn ON the positioning start signal.
3)
Setting
value
9003
Set the start No. "9003" for the new current value.
50000
Set the new "[Md.20] Current feed value".
V
Current feed value
Md.20
Positioning start No.
Cd.3
Current value changing
Cd.9
CHAPTER 9 MAJOR POSITIONING CONTROL
Setting details
Start of data No. 9003
Address during positioning
execution
Data No. during positioning
execution
Buffer memory address
Axis 1
Axis 2
Axis 3
Axis 4
1500
1600
1700
1800
1506
1606
1706
1806
1507
1607
1707
1807
t
50000
9003
50000
449
9