(e) [Md.12] Axis error occurrence (Minute:second)
Item
Storage details
Stores the time (Minute:second) at which an axis error was detected.
■Monitoring is carried out with a hexadecimal display.
Buffer memory (stored with BCD code)
Reading the monitor
4
value
b15
b12
0
1 0 0 1 0 0 1 0 0 0 0 0 1 1 1
0 to 5
Default value
0000H
Storage buffer memory
For details on the storage buffer memory, refer to the following.
address
Page 187, Section 5.6.1 (3)
(Common to axes 1 to 4)
(f) [Md.13] Error history pointer
Item
Storage details
Indicates a pointer No. that is next to the Pointer No. assigned to the latest of the existing records.
■Monitoring is carried out with a decimal display.
Reading the monitor
Monitor value
value
Default value
0
Storage buffer memory
address
1357
(Common to axes 1 to 4)
9
0
7
b8
b4
b0
4
0 to 9
0 to 5
0 to 9
00 to 59 (minute)
Storage value (Pointer number)
0 to 15
CHAPTER 5 DATA USED FOR POSITIONING CONTROL
Description
Monitor value
9
0
7
00 to 59 (second)
Description
5
189