(1) Independent positioning control (Positioning complete)
This control is set when executing only one designated data item of positioning. If a dwell time is designated, the
positioning will complete after the designated time elapses.
This data (operation pattern [00] data) becomes the end of block data when carrying out block positioning. (The
positioning stops after this data is executed.)
Positioning start signal
[Y10, Y11, Y12, Y13]
Start complete signal
[X10, X11, X12, X13]
[XC, XD, XE, XF]
BUSY signal
Positioning complete signal
[X14, X15, X16, X17]
V
Positioning complete (00)
ON
OFF
ON
OFF
ON
OFF
OFF
CHAPTER 9 MAJOR POSITIONING CONTROL
Dwell time
Time
ON
9
343