(4) [Pr.32] JOG operation acceleration time selection
Set which of "acceleration time 0 to 3" to use for the acceleration time during JOG operation.
0: Use the value set in "[Pr.9] Acceleration time 0".
1: Use the value set in "[Pr.25] Acceleration time 1".
2: Use the value set in "[Pr.26] Acceleration time 2".
3: Use the value set in "[Pr.27] Acceleration time 3".
(5) [Pr.33] JOG operation deceleration time selection
Set which of "deceleration time 0 to 3" to use for the deceleration time during JOG operation.
0: Use the value set in "[Pr.10] Deceleration time 0".
1: Use the value set in "[Pr.28] Deceleration time 1".
2: Use the value set in "[Pr.29] Deceleration time 2".
3: Use the value set in "[Pr.30] Deceleration time 3".