Mitsubishi Electric MELSEC-L LD75P User Manual page 230

Positioning module
Hide thumbs Also See for MELSEC-L LD75P:
Table of Contents

Advertisement

(26)[Cd.28] Target position change value (new speed)
Item
• When changing the target position during a positioning operation, use this data item to specify a new speed. ( Page 228,
Setting details
Section 5.7.2 (26) (a))
• The speed will not change if "0" is set.
■Set with a decimal.
Actual value
Setting value
Setting value
(Decimal)
Default value
0
Axis 1: 1536, 1537
Storage buffer memory
Axis 2: 1636, 1637
address
Axis 3: 1736, 1737
Axis 4: 1836, 1837
(a) Setting range
[Pr.1] Unit setting
0: mm
1: inch
2: degree
3: pulse
228
Cd. 28 Target position change value (speed)
Conversion into an integer value
n
× 10
R
Example: If " Cd. 28 Target position change
value (speed)" is set as "10000.00",
the buffer memory stores
"1000000".
Description
Unit conversion table ( Cd.28 )
n
Unit
mm/min
-2
inch/min
-3
degree/min
-3
pulse/s
0
Setting range
-2
0 to 2000000000 (10
mm/min)
-3
0 to 2000000000 (10
inch/min)
-3
0 to 2000000000 (10
degree/min)
0 to 4000000 (pulse/s)