Displaying The Alarm History - YASKAWA SGD7S Product Manual

Servopack with mechatrolink-iii
Hide thumbs Also See for SGD7S:
Table of Contents

Advertisement

12.2.4

Displaying the Alarm History

The alarm history displays up to the last ten alarms that have occurred in the SERVOPACK.
Note: The following alarms are not displayed in the alarm history: A.E50 (MECHATROLINK Synchronization Error),
A.E60 (Reception Error in MECHATROLINK Communications), and FL-1 to FL-5.
Preparations
No preparations are required.
Applicable Tools
The following table lists the tools that you can use to display the alarm history and the applica-
ble tool functions.
Tool
Digital Operator
SigmaWin+
Operating Procedure
Use the following procedure to display the alarm history.
1.
Click the
maWin+.
2.
Select Display Alarm in the Menu Dialog Box.
The Alarm Display Dialog Box will be displayed.
3.
Click the Alarm History Tab.
The following display will appear and you can check the alarms that occurred in the past.
1. If the same alarm occurs consecutively within one hour, it is not saved in the alarm history.
Information
2. You can clear the alarm history by clicking the Clear Button. The alarm history is not
This concludes the procedure to display the alarm history.
Function
Fn000
Alarm − Display Alarm
Servo Drive Button in the workspace of the Main Window of the Sig-
If it occurs after an hour or more, it is saved.
cleared when alarms are reset or when the SERVOPACK main circuit power is turned OFF.

12.2.4 Displaying the Alarm History

Σ
-7-Series Digital Operator Operating Manual
(Manual No.: SIEP S800001 33)
Operating Procedure
Alarm number: Alarm name
Alarms in order of occurrence
(Older alarms have higher numbers.)
12.2 Alarm Displays
Reference
on page 12-43
12
12-43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents