9.2.3

I/O Signal Monitor

Use the following procedure to check I/O signals.
1.
Click the
maWin+.
2.
Select Wiring Check in the Menu Dialog Box.
The Wiring Check Dialog Box will be displayed.
3.
Click the Monitor Mode Button.
Input signal status
You can also use the above window to check wiring.
Information
• Checking Input Signal Wiring
• Checking Output Signal Wiring
Servo Drive Button in the workspace of the Main Window of the Sig-
Change the signal status at the host controller. If the input signal status on the window
changes accordingly, then the wiring is correct.
Click the Force Output Mode Button. This will force the output signal status to change. If
the signal status at the host controller changes accordingly, then the wiring is correct.
You cannot use the Force Output Mode Button while the servo is ON.
Output signal status
9.2 Monitoring SERVOPACK Status

9.2.3 I/O Signal Monitor

9
9-5