6.1 I/O Signal Allocations
6.1.10 Speed Limit during Torque Control
Selecting the Speed Limit
The smaller of the external speed limit and internal speed limit will be used.
Pn002
Internal Speed Limiting
Set the speed limit for the motor in Pn407 (Speed Limit during Torque Control) or Pn480
(Speed Limit during Force Control).
Also set Pn408 = n.X (Speed Limit Selection) to specify using the maximum motor speed
or the overspeed alarm detection speed as the speed limit. Select the overspeed alarm detec-
tion speed to limit the speed to the equivalent of the maximum motor speed.
Pn408
Note: If you are using a Rotary Servomotor, set Pn407 (Speed Limit during Torque Control). If you are using a Linear
Servomotor, set Pn480 (Speed Limit during Force Control).
• Rotary Servomotors
Pn407
• Linear Servomotors
Pn480
Note: If the parameter setting exceeds the maximum speed of the Servomotor, the Servomotor's maximum speed
or the overspeed alarm detection speed will be used.
External Speed Limiting
The motor speed will be limited by VLIM (Limit Speed for Torque Control). Refer to the following
manual for details.
Σ-7-Series MECHATROLINK-III Communications Standard Servo Profile Command Manual (Manual No.: SIEP
S800001 31)
6-14
Parameter
n.
0
Reserved settings (Do not use.)
Use the speed limit from the VLIM (Limit
n.
1
Speed for Torque Control) command as the
(default setting)
speed limit. (Use external speed limiting.)
Parameter
Use the smaller of the maximum motor speed
n.0
and the setting of Pn407 or Pn480 as the
(default setting)
speed limit.
Use the smaller of the overspeed alarm detec-
n.
1
tion speed and the setting of Pn407 or Pn480
as the speed limit.
Speed Limit during Torque Control
Setting Range
0 to 10,000
Speed Limit during Force Control
Setting Range
0 to 10,000
Meaning
Meaning
Setting Unit
Default Setting
-1
10000
1 min
Setting Unit
Default Setting
1 mm/s
10000
When Enabled
Classification
After restart
Setup
When Enabled
Classification
After restart
Setup
Torque
When Enabled
Classification
Immediately
Setup
Force
When Enabled
Classification
Immediately
Setup