5.12 Holding Brake

5.12.3 Output Timing of /BK (Brake) Signal When the Servomotor Is Stopped

5.12.3 Output Timing of /BK (Brake) Signal When the
Servomotor Is Stopped
When the Servomotor is stopped, the /BK signal turns OFF as soon as the SV_OFF (Servo
OFF) command is received. Use the servo OFF delay time (Pn506) to change the timing to turn
OFF power supply to the motor after the SV_OFF command is input.
Pn506
• When the Servomotor is used to control a verti-
cal axis, the machine moving part may move
slightly due to gravity or an external force.
You can eliminate this slight motion by setting
the servo OFF delay time (Pn506) so that
power supply to the motor is stopped after the
brake is applied.
• This parameter sets the timing of stopping
power supply to the Servomotor while the Ser-
vomotor is stopped.
Important
5.12.4 Output Timing of /BK (Brake) Signal When the
Servomotor Is Operating
If an alarm occurs while the Servomotor is operating, the Servomotor will start stopping and the
/BK signal will be turned OFF. You can adjust the timing of /BK signal output by setting the
brake reference output speed level (Rotary Servomotors: Pn507, Linear Servomotors: Pn583)
and the Servo OFF-Brake Command Waiting Time (Pn508).
Note: If zero-speed stopping is set as the stopping method for alarms, the setting of Pn506 (Brake Reference-
Servo OFF Delay Time) is used after the motor stops.
• Rotary Servomotors
Pn507
Pn508
• Linear Servomotors
Pn583
Pn508
5-34
Brake Reference-Servo OFF Delay Time
Setting Range
Setting Unit
0 to 50
Power supply to the Servomotor will be stopped immediately when an alarm occurs, regardless
of the setting of this parameter. The machine moving part may move due to gravity or an external
force before the brake is applied.
Brake Reference Output Speed Level
Setting Range
Setting Unit
0 to 10,000
Servo OFF-Brake Command Waiting Time
Setting Range
Setting Unit
10 to 100
Brake Reference Output Speed Level
Setting Range
Setting Unit
0 to 10,000
Servo OFF-Brake Command Waiting Time
Setting Range
Setting Unit
10 to 100
Default Setting
10 ms
0
SV_OFF (Servo OFF)
command input
Motor power status
Default Setting
-1
100
1 min
Default Setting
10 ms
50
Default Setting
1 mm/s
10
Default Setting
10 ms
50
Speed
Position
When Enabled
Immediately
Servo ON
ON (Brake
OFF (Brake applied.)
/BK signal
released.)
Power supplied
to motor.
Pn506
Speed
Position
When Enabled
Immediately
Speed
Position
When Enabled
Immediately
Speed
Position
When Enabled
Immediately
Speed
Position
When Enabled
Immediately
Torque
Classification
Setup
Servo OFF
Power not
supplied to
motor.
Torque
Classification
Setup
Torque
Classification
Setup
Force
Classification
Setup
Force
Classification
Setup