8.4.2

Operating Procedure

The tuning-less function is enabled in the default settings. No specific procedure is required.
You can use the following parameter to enable or disable the tuning-less function.
Parameter

n.

n.
(default setting)
Pn170

n.
(default setting)

n.
When you enable the tuning-less function, you can select the tuning-less type. Normally, set
Pn14F to n.2 (Use tuning-less type 3) (default setting). If compatibility with previous mod-
els is required, set Pn14F to n.0 (Use tuning-less type 1) or n.1 (Use tuning-less
type 2).
Parameter

n.

n.
Pn14F

n.
(default setting)
Tuning-less Level Settings
If vibration or other problems occur, change the tuning-less levels. To change the tuning-less
levels, use the SigmaWin+.
 Preparations
Always check the following before you set the tuning-less levels.
• The tuning-less function must be enabled (Pn170 = n.1).
• The test without a motor function must be disabled (Pn00C = n.0).
 Procedure
Use the following procedure to set the tuning-less levels.
In addition to the following procedure, you can also set the parameters directly. Refer to
Related Parameters, below, for the parameters to set.
1.
Select Setup - Tuning-less Level Setting in the Menu Dialog Box of the SigmaWin+.
The Response Level Setting Dialog Box will be displayed.
0
Disable tuning-less function.
1
Enable tuning-less function.
0
Use for speed control.
Use for speed control and use host controller
1
for position control.
0
Use tuning-less type 1.
Use tuning-less type 2. (The noise level is
1
improved more than with tuning-less type 1.)
2
Use tuning-less type 3.
Meaning
Meaning
8.4 Tuning-less Function

8.4.2 Operating Procedure

When Enabled
Classification
After restart
Setup
When Enabled
Classification
After restart
Tuning
8
8-13