4 Faults and alarms
4.2 List of faults and alarms
A01317 (N)
Deactivated component again present
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
If a component of the target topology for an active drive object is inserted and the associated parameter of the
component is set to "deactivate" (p0125, p0145, p0155, p0165).
Note:
This is the only message that is displayed for a deactivated component.
Remedy:
The alarm automatically disappears again with the following actions:
- activate the components involved (p0125 = 1, p0145 = 1, p0155 = 1, p0165 = 1).
- again withdraw the component involved.
See also: p0125 (Activate/deactivate power unit components), p0145 (Activate/deactivate encoder interface), p0155
(Voltage Sensing Module activate/deactivate)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A01318
BICO: Deactivated interconnections present
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
This alarm is used in the following cases:
- if an inactive/non-operational drive object is active again/ready for operation
- if there are items in the list of BI/CI parameters (r9498[0...29], r9499[0...29])
- if the BICO interconnections saved in the list of BI/CI parameters (r9498[0...29], r9499[0...29]) have actually been
changed
Remedy:
Reset alarm:
- set p9496 to 1 or 2
or
- deactivate the drive object again.
A01319
Inserted component not initialized
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, ENC, HUB, TB30, TM120, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
Initialization is required for at least one inserted component.
This is only possible if the pulses are inhibited for all the drive objects.
Remedy:
Activate pulse inhibit for all drive objects.
1400
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
GLOBAL
List Manual (LH2), 07/2016, A5E03263479A
SINAMICS G130/G150