SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
A seismic manual test with the keypad can be done by the engineer in Full Engineer mode, and also by a
user of type Manager or type Standard:
An engineer is able to test all sensors in all areas configured in the system using any keypad.
l
A user is able to test only the sensors in areas that are both assigned to him and to the particular
l
keypad he is using.
To perform a seismic test in Engineer mode, select FULL ENGINEER > TEST > SEISMIC TEST.
To perform a seismic test in User mode, select MENUS > TEST > SEISMIC TEST.
Note: The following instructions apply to both engineer and user modes but note that only a subset of
options may be available to a user.
The following options are available in the SEISMIC TEST menu:
TEST ALL AREAS
l
Tests seismic zones in all available areas if there is more than one area that contains seismic
zones.
'AREA NAME'
l
The names of the areas containing seismic zones are listed individually. When a specific area is
selected, the following options are available:
– TEST ALL ZONES
Test all seismic zones in this area if there is more than one seismic zone.
– 'ZONE NAME'
The names of all seismic zones are listed and can be selected for testing individually.
The message 'SEISMIC TEST' is display on the keypad while the test is being performed,
If the test fails, the message 'SEISMIC FAIL' is displayed. If the "i" or VIEW key is pressed, a list of the
failed zones is displayed which can be scrolled through.
If the test succeeds, 'SEISMIC OK' is displayed.
Entries are recorded in the event log with the following details:
user who initiated the test
l
result (OK or FAIL)
l
area and zone number and name
l
No events are reported for manual tests.