Vanderbilt SPC4 Series Installation & Configuration Manual page 336

Table of Contents

Advertisement

SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Receiver ID Address
Receiver IP Port
Always Connected
Panel Master
Polling Interval
Polling Trigger
Generate a Network
Fault
Dial-up (Applies to the GPRS modem connection only)
Dial-up Enable
Call type
GPRS protocol
GPRS address
GPRS port
GPRS Hangup
Timeout
GPRS Autoconnect
Dial-up on Net Fault
Dial-up Interval 1*
Dial-up Interval 2*
Network Address*
Phone Number*
© Vanderbilt 2018
Enter the IP address of the receiver.
Enter the IP port that the EDP receiver is listening on.
If enabled the panel will keep a permanent connection to the
receiver. If disabled, the panel will only connect to the receiver after
an alarm event.
If enabled the panel is master of polling messages. Only applicable
to UDP connections.
Enter the number of seconds between polls.
Enter the number of missing polls before a network connection fail
is registered. Only applicable to UDP connections.
If polling fails, a network fault alert is generated.
Check this box to report events through a dial-up connection.
Select type of call to use when dial up is enabled. Select GPRS.
Select the transport layer protocol used over the GPRS connection.
Options are UDP or TCP. Only applicable if Call Type is GPRS.
Enter the IP address of EDP receiver for GPRS connections. Only
applicable if Call Type is GPRS.
Enter the port that the EDP receiver is listening on for GPRS
connections Options are UDP or TCP. Only applicable if Call Type
is GPRS. Default is 50000.
Enter the time in seconds after which the GPRS call will hang up.
(0 = stay connected until IP connection is up)
Check this box to automatically trigger a GPRS call to the server if
an IP network fault occurs.
Check this box to report network faults on a dial-up test call.
Enter the number of minutes between dial-up test calls when
network link is up.
Enter number of minutes between dial-up test calls when network
link is down.
Enter the IP address of the receiver. This is only required if the
connection to the EDP receiver is being made over the Ethernet
interface. If using one of the on-board modems then leave this field
blank.
Enter the first phone number that the modem(s) will dial to contact
the receiver.