Vanderbilt SPC4 Series Installation & Configuration Manual page 292

Table of Contents

Advertisement

SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
7. Select an output from the drop-down list.
8. Click Add to add a new gate or Save to save the new settings for an existing gate.
See also
Triggers below
17.10.7.3 Triggers
A trigger is a system state (for example, zone closing/time/system event (alarm), etc.) that can be used as
inputs to the Cause & Effects. The triggers can be logically assigned together using the logical operators
AND/OR to create user outputs. The system supports up to a maximum of 1024 triggers across all its
Cause & Effects system.
1. Select Configuration > Advanced > Triggers.
The following page will be displayed.
2. Configure the fields as described in the table below.
Trigger
Description Enter a text description for the trigger.
Calendar
Time limit
Timer
Trigger
Operation
© Vanderbilt 2018
System generated number for new trigger.
Trigger will only become active if one of the 2 optional steps (calendar/time
limitation) is configured
Select a calendar, if required. If selected, the trigger will only be in effect during
this calendar period. See Calendars on page 287.
Select a time period between 00:00 and 24:00 during which the trigger will only be
in effect. The Start time is inclusive, the end time is exclusive.
Note: This parameter delays a trigger transition from ON to OFF only; from OFF
to ON is immediate.
Enter the number of seconds that the trigger conditions must be true before the
trigger will activate.
All All trigger conditions must be active for the system to activate the
l
trigger.
Any Any trigger condition that is active enables the system to activate the
l
trigger.