SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Output Type
Description
Entry Status
This output activates if an 'All Okay' entry procedure is implemented and there is no alarm
generated, that is, the 'All Okay' button is pressed within the configured time after the user code is
entered.
Warning
This output activates if an 'All Okay' entry procedure is implemented and a silent alarm generated,
Status
that is, the 'All Okay' button is not pressed within the configured time after the user code is
entered.
Ready to Set
This output activates when an area is ready to set.
Setting ACK
This output signals the setting status. The output toggles for 3 seconds to signal that the setting
has failed. The output remains on for 3 seconds if setting is successful.
Fullset Done
This output activates for 3 seconds to signal that the system has been fullest.
Blockschloss
Used for normal Blockschloss devices.
1
When all zones in an area are closed, and there are no pending faults, the 'Blockschloss 1' output
is activated. If the lock on the Blockschloss is closed, a 'Keyarm' input is activated, the relevant
area is set and the 'Setting Ack' output is activated for 3 seconds to signal that the setting was
successful. 'Blockschloss 1' is not deactivated.
If the Blockschloss is unlocked, the Blockschloss device deactivates the Keyarm input to the
unset state (closed) and the area is unset. 'Blockschloss 1' is then deactivated.
Blockschloss
Used for Blockschloss device type - Bosch Blockschloss, Sigmalock Plus, E4.03.
2
When all zones in an area are closed, and there are no pending faults, the 'Blockschloss 2' output
is activated. If the lock on the Blockschloss is closed, a 'Keyarm' input is activated, the relevant
area is set and the 'Setting Ack' output is activated for 3 seconds to signal that the setting was
successful. 'Blockschloss 2' is then deactivated.
If the Blockschloss is unlocked, the Keyarm zone is switched to unset (closed) and the area is
unset. 'Blockschloss 2' is activated (if area is ready to set).
Lock Element
Activates if the Lock Element is in the 'locked' position.
Unlock
Activates if the Lock Element is in the 'unlocked' position.
Element
Code Tamper
Activates if there is a code tamper in the area. Clears when state is reset.
Trouble
Activates if any zone is in trouble state.
Ethernet Link
Activates if there is a fault on the Ethernet link.
Network Fault Activates if there is an EDP communications fault.
Glass Reset
Used to switch on the power for the glassbreak interface module and to remove power in order to
reset the device. The output is reset if a user enters their code, the zone is not in the closed state,
and the bells deactivated.
Confirmed
Activates in the following scenarios for PD6662 compliance:
holdup
two hold-up zone activations more than two minutes apart
l
a hold-up zone and a panic zone activation more than two minutes apart
l
if a hold-up zone and a tamper zone or a panic zone and a tamper zone activation occurs
l
within the two minute period