Vanderbilt SPC4 Series Installation & Configuration Manual page 198

Table of Contents

Advertisement

SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
The following page is displayed.
3. Enter a User ID that is not currently being used. If you enter an ID that is already used, an 'Invalid
ID' message is displayed when you select Generate PIN.
4. Provide a User Name (maximum 16 characters and case sensitive).
5. To automatically generate a User PIN for a new user, click the Generate PIN button. Change the
PIN if required. Enter 0 if PIN is not required.
Note: To comply with INCERT approvals, the user's PIN code must contain more than 4 digits.
6. You can also limit access to the system for this user by ticking the Date Limit box and entering a
To and From date in the date fields.
User Alerts displays the status of the user's PIN. For example, It displays the number of days
remaining before the PIN expires, if Periodic changes are enabled in the system PIN Policy.
7. You can enable the Alarm Access option to grant time-limited access to the system for this user
within a specific window.
The time limits for this option are set in the System Timers page. Go to
Configuration>System>System Timers to configure this option. See Timers on page 264.
8. Select the appropriate user profile (see Adding/Editing User Profiles on page 200) for this user.
9. Select Duress Enable for this user if required. The number of PINs allocated for duress (PIN +1 or
PIN+2) is set in system options (see Options on page 255).
The Duress option is only available on this page if User Duress is enabled for the system in System
Options. If Duress is enabled for this user, then consecutive user PINs for other users (for example,
2906, 2907) are not permitted, as entering this PIN from the keypad would activate a user duress
event.
Access Control
Attribute
Description
Card
Enter card number. Enter 0 to unassign this card.
Number
© Vanderbilt 2018
In normal mode any user with this attribute selected is unable to access the
system.