Encoder Calibration - JVL MIS17 Series User Manual

Integrated step motors, including step motor controller smc66, smc85
Table of Contents

Advertisement

17.4
17.4.1
Procedure to calibrate encoder
Normally the encoder (H2, H3 or H4 option) is calibrated from the factory but it can be
required to recalibrate for example if the encoder firmware have been updated from an
older version.
If the error message "Encoder lost position" is shown its required that the following cali-
bration procedure takes place.
Step 1
Make sure the motor is free from any load and can rotate without any
mechanical resistance.
Step 2
Press «Reset position»
Step 3
Press «Clear errors»
Any errors shown should now
disappear.
Step 4
Now go to the
write
hit enter.
The motor will now move 10 fast
revolutions and 1 slow. This takes
approx. 2 minutes and when finished
the motor stands still and the actual
position is approximately 409500.
Now the calibration is finished and the
position can be reset if needed.
354
JVL Industri Elektronik A/S - User Manual - Integrated Stepper Motors MIS17x, 23x, 34x, 43x

Encoder calibration

«Advanced»
tab and
350
in the Command field and
Finished !
TT2554-01GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents