Technical Data - ABB RELION RED670 Series Product Manual

Line differential protection
Hide thumbs Also See for RELION RED670 Series:
Table of Contents

Advertisement

Line differential protection RED670 2.2
Product version: 2.2

24. Technical data

General
Definitions
Reference value
The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range
The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements
Operative range
The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Presumptions for Technical Data
The technical data stated in this document are only valid
under the following circumstances:
1. Main current transformers with 1 A or 2 A secondary
rating are wired to the IED 1 A rated CT inputs.
2. Main current transformer with 5 A secondary rating are
wired to the IED 5 A rated CT inputs.
3. CT and VT ratios in the IED are set in accordance with
the associated main instrument transformers. Note that
for functions which measure an analogue signal which
do not have corresponding primary quantity the 1:1 ratio
shall be set for the used analogue inputs on the IED.
Example of such functions are: HZPDIF, ROTIPHIZ and
STTIPHIZ.
4. Parameter
IBase used by the tested function is set
equal to the rated CT primary current.
5. Parameter
UBase used by the tested function is set
equal to the rated primary phase-to-phase voltage.
ABB
M10993-1 v3
GUID-1E949E38-E04D-4374-A086-912C25E9F93C v2
SBase used by the tested function is set
6. Parameter
equal to:
– √3 ×
IBase × UBase
7. The rated secondary quantities have the following
values:
– Rated secondary phase current I
depending on selected TRM.
– Rated secondary phase-to-phase voltage U
the range from 100 V to 120 V.
– Rated secondary power for three-phase system S
√3 × U
× I
r
r
8. For operate and reset time testing, the default setting
values of the function are used if not explicitly stated
otherwise.
9. During testing, signals with rated frequency have been
injected if not explicitly stated otherwise.
1MRK 505 379-BEN C
IP11376-1 v2
is either 1 A or 5 A
r
is within
r
=
r
57