When connecting the brake unit (FR-BU(H)/MT-BU5) to improve the brake capability at deceleration, make connection
as shown below.
(1) Connection with the FR-BU (FR-A720-02150 (FR-A740-01100) or lower)
Three-phase AC
power supply
*1
Connect the inverter terminals (P/+, N/-) and brake unit (FR-BU (H)) terminals so that their terminal signals match with each other.
(Incorrect connection will damage the inverter.)
*2
When the power supply is 400V class, install a step-down transformer.
*3
Be sure to remove the jumper across terminals PR and PX when using the FR-BU with the inverter of FR-A720-00330 (FR-A740-
00170) o lower.
*4
The wiring distance between the inverter, brake unit (FR-BU) and resistor unit (FR-BR) should be within 5m(16.4 feet). If twisted
wires are used, the distance should be within 10m(32.8feet).
CAUTION
 If the transistors in the brake unit should become faulty, the resistor can be unusually hot, causing a fire. Therefore, install a
magnetic contactor on the inverter's input side to configure a circuit so that a current is shut off in case of fault.
 Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.
MCCB
R/L1
S/L2
T/L3
Inverter
PR
*3
PX
Connection of stand-alone option units
T
*2
MC
FR-BR
Motor
U
P
V
IM
PR
W
FR-BU
PR
P/+
*1
N/−
N/−
*4
5m (16.4 feet)
or less
ON
OFF
MC
TH1
TH2
HA
HB
HC
45
2