Commissioning
All e!RUNTIME applications are reset with a cold start reset. All global data and
the retain variables are set to their initialization values.
This corresponds to the e!COCKPIT IDE "Reset Cold" command.
</dg_
To perform a cold start reset, set the mode selector switch to "Reset" and hold it
there for more than seven seconds.
Execution of the reset is signaled after seven seconds by the "RUN" LED going
out for an extended period. You can then release the mode selector switch.
</dg_
7.7.3

Software Reset

The controller is restarted on a software reset.
To perform a software reset, set the mode selector switch to RUN or STOP and
then press the Reset button (RST) for one to eight seconds.
All LEDs will light up briefly in green to signal reset completion.