Table 205: MODBUS RTU Settings

Parameters
RTU mode
Device ID
Maximum
response time
Interface
Baud rate
Stop bits
Parity
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
Explanation
Enable for the MODBUS RTU mode
*
Off
Operation not permitted
Active
Operation possible
Device ID (device address) for the tty device
*
1
min. device ID
247
max. device ID
Response timeout for a request in [ms]
2000
min. response time = 2 seconds. If this value is
set lower than 2 seconds, it will be corrected
internally to 2 seconds.
*
5000
Default = 5 seconds
4294967295
max. response time > 71 hours.
Device name
"dev/..."
Name of the tty in the string
*
"dev/ttyO0"
Standard tty
Communication baud rate
1200 baud
1200 baud min. transmission speed
2400 baud
2400 baud
4800 baud
4800 baud
9600 baud
9600 baud
19200 baud
19200 baud
38400 baud
38400 baud
57600 baud
57600 baud
*
115200 baud
115200 baud, max. transmission speed
Number of stop bits
*
1 stop bit
1 stop bit in the frame; must be used when even
or odd parity has been selected.
2 stop bits
2 stop bits in the frame; must be used when
"None" has been selected for parity.
Parity check
None
No parity check performed; 2 stop bits must be
selected in the configuration for this setting.
*
Even
Even parity
Odd
Odd parity
MODBUS – CODESYS 2 281