Modbus Settings; Table 202: Modbus Settings - WAGO 750-8207 Manual

Pfc200 cs 2eth rs 3g plc - controller pfc200
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-8207 PFC200 CS 2ETH RS 3G
10.3.1

MODBUS Settings

The "MODBUS settings" group contains the following configuration parameters.

Table 202: MODBUS Settings

Parameters
PLC stop
behavior
Fieldbus error
response
*
Default setting
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
Explanation
Response of the MODBUS slave when the controller has halted
(controller in STOP state)
No data
No data exchange possible. MODBUS requests
exchange
will always be answered by the exception
response "ILLEGAL FUNCTION" (0x81).
Switch to
Data exchange possible. Substitute values (0)
substitute
are provided for MODBUS read requests and the
*
value
values accepted unchanged in the local
MODBUS process image for write requests,
without passing these on to the controller.
Hold last value Data exchange possible. The last frozen values
are provided for MODBUS read requests and the
values accepted unchanged in the MODBUS
process image for write requests, without passing
these on to the controller.
Response of the MODBUS slave to detected fieldbus errors
(interruption of communication).
No data
No data exchange possible.
exchange
Switch to
Data exchange possible. Substitute values (0)
substitute
are supplied from the MODBUS process image
*
value
for PLC read functions; for write access the
values are accepted unchanged in the MODBUS
process image without passing them on to the
MODBUS master.
Hold last value Data exchange possible. The previously frozen
values are supplied from the MODBUS process
image for PLC read functions; for write access
the values are accepted unchanged in the
MODBUS process image without passing them
on to the MODBUS master.
MODBUS – CODESYS 2 279