Table 301: Description of the Configuration Scripts for "Networking - ETHERNET"

Parameters Status Call-Up
Switch Configuration
Interface Mode
Interface X1
Port State
Autonegotiation
Speed and
Duplex Settings
Interface X2
See "Interface X1". When calling these up, replace "X1" with "X2".
</dg_
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
read
get_dsa_mode
set_dsa_mode -v
write
<value>
get_eth_config
read
X1 state
config_ethernet port=X1
state=enabled
write
config_ethernet port=X1
state=disabled
get_eth_config
read
X1 autoneg
config_ethernet port=X1
autoneg=on
config_ethernet port=X1
write
autoneg=off
speed=<value>
duplex=<value>
get_eth_config
read
X1 speed
get_eth_config
read
X1 duplex
config_ethernet port=X1
autoneg=off
write
speed=<value>
duplex=<value>
Appendix 383
Output/Input
Query the switch
configuration:
Possible return values:
-
0 = „switched" mode
-
1 = „separated" mode
Set the switch configuration:
Possible entries for <value>:
-
0 = „switched" mode
-
1 = „separated" mode
Query the port state:
Possible return values:
-
enabled
-
disabled
Activate port: enabled
Deactivate port: disabled
Query the status of the
autonegotiation function:
Possible return values:
-
on
-
off
Activate the autonegotiation
function: on
Deactivate the autonegotiation
function: off
Note: You must also indicate
the speed and duplex value
when you deactivate the
autonegotiation function.
Possible entries for speed:
-
10M
-
100M
Possible entries for duplex:
-
half
-
full
Display of ETHERNET speed
Display of the Duplex mode
Change the ETHERNET
speed and the Duplex mode.
Possible entries for speed:
-
10M
-
100M
Possible entries for duplex:
-
half
-
full
Effective
Immediately
Immediately
Immediately