3.9.7

ETHERNET

Table 25: Technical Data – ETHERNET
ETHERNET
Transmission medium
Baud rate
Protocols
MODBUS input and
output process image,
max.
No direct access from fieldbus to the process image for I/O modules!
Any data that is required from the I/O module process image must be explicitly
mapped in the CODESYS program to the data in the fieldbus process image and
vice versa! Direct access is not possible!
3.9.8

Serial interface

Table 26: Technical Data – Serial Interface
Interface
Protocols
3.9.9

Mobile Radio Modem

Table 27: Technical Data – Mobile Radio Modem
Technology
SIM card type / slot
Communication
Communication types
3.9.10

Connection Type

Table 28: Technical Data – Field Wiring
Wire connection
Cross section
Stripped lengths
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
2 x RJ-45 (switched or separated mode)
Twisted Pair S-UTP, 100 Ω, Cat 5,
100 m maximum cable length
10/100 Mbit/s; 10Base-T/100Base-TX
DHCP, DNS, SNTP, FTP, FTPS (only
explicit connections), SNMP, HTTP,
HTTPS, SSH, MODBUS (TCP, UDP)
CODESYS 2 1,000 words,
also with MODBUS access to the flag
area (see Section "MODBUS" > ... >
"Flag Area")
e!RUNTIME
32,000 words
1 x serial interface per TIA/EIA 232 and
TIA/EIA 485 (switchable), 9-pole D-sub
female connector
MODBUS RTU
GSM / Edge / UMTS / HSPA+
Mini SIM, push-push mechanism
Quad band
SMS (bidirectional),
GPRS connection to the Internet
CAGE CLAMP
0.08 mm² ... 2.5 mm², AWG 28 ... 14
8 mm ... 9 mm / 0.33 in