Technical Data; Device Data; System Data; Power Supply - WAGO 750-8207 Manual

Pfc200 cs 2eth rs 3g plc - controller pfc200
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-8207 PFC200 CS 2ETH RS 3G
3.9

Technical Data

3.9.1

Device Data

Table 19: Technical Data − Device Data
Width
Height (from upper edge of DIN 35 rail)
Length
Weight
</dg_
3.9.2

System Data

Table 20: Technical Data – System Data
CPU
Operating System
Memory card slot
Type of memory card
3.9.3

Power supply

Table 21: Technical Data – Power Supply
Power supply
Max. input current (24 V)
Power failure time acc. IEC 61131-2
Total current for I/O modules (5V)
Isolation
Buffer for system power supply!
The system power supply must be buffered to bridge power outages. As the
power demand depends on the respective node configuration, buffering is not
implemented internally.
To achieve power outages of 1 ms to 10 ms according to IEC61131-2, determine
the buffering appropriate for your node configuration and structure it as an
external circuit.
</dg_
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
Device Description
103 mm
65 mm
100 mm
288 g
Cortex A8, 600 MHz
®
Real-time Linux
3.18 (with RT
Preemption Patch)
Push-push mechanism, sealable cover
lid
SD and SDHC up to 32 Gbytes
(All guaranteed properties are valid only
in connection with the WAGO 758-
879/000-001 memory card.)
24 VDC (-25 % ... +30 %)
550 mA
Depending on external buffering
1700 mA
500 V system/supply
49
Manual

Advertisement

Table of Contents
loading

Table of Contents