Eliminating Errors in CODESYS Web Visualization

If you are experiencing problems when working with the CODESYS Web
visualization, use the following table to find the solution. If you cannot eliminate
the problem, please contact WAGO support.

Table 200: Errors and Remedies

Error
Internet Explorer reports
the error "APPLET NOT
INITIATED"
Web visualization is not
displayed
Web visualization
"freezes".
Web visualization stops
after an extended period
of time.
Web visualization
cannot be loaded into
the controller
Bitmap is not displayed
Java console reports:
"Class not found"
Web visualization is
static, all process values
are "0"
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
Run-time System CODESYS 2.3 271
Solution
Close all Internet Explorer windows and restart. If the error persists, this
indicates a missing or damaged file.
Using FTP, check if the entire Java archive "webvisu.jar" is available in
the "/PLC" folder of the controller. The original file can be found in the
installation path of CODESYS (usually under C:\Programme\WAGO
Software\CODESYS V2.3\Visu\webvisu.jar).
If necessary, replace the damaged file using FTP or force the download
of all files in CODESYS with Purge All > Compile All > Log in.
Have you installed the JRE? Check the firewall settings, e.g., if port 8080
is open.
The call-up intervals selected in the task configuration are too small. As a
result, the Web server of the controller — which is executed with a low
priority — does not receive sufficient computer time, if any at all.
If no (explicit) task configuration has been provided, the PLC_PRG is
(implicitly) executed as a free running task with Priority 1. This
significantly limits the Web server's computing time. Always provide a
task configuration when using Web visualization. In doing so, the call-up
interval should not exceed three times the average execution time.
When determining the execution time, ensure that the PLC program has
reached a "steady state." When determining the execution time, ensure
that the PLC program is not "steady state."
Not all files may fit into the controller's file system. Delete any unneeded
data (e.g., via FTP).
If the name of an image file contains umlauts, the Web server cannot
interpret these image names.
The JRE does not find the entry point for the class "webvisu.class" in the
Java archive "WebVisu.jar". The Java archive is probably incomplete.
Delete "WebVisu.jar" from the Java cache and/or deactivate the cache.
In this case, the controller requests the archive (applet) again. If the
problem persists, reload the project into the controller.
Process data communication has failed.
If Web visualization is operated over a proxy server, then a SOCKS
proxy is also necessary for process data exchange in addition to the
actual HTTP proxy.