Table 234: Error Code 1, Explanation of Blink Codes and Procedures for Troubleshooting
Error
Argument
-
1
2
3
4
5
6
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
Cause
Invalid parameter
checksum for internal
data bus interface
Internal buffer
overflow (max.
amount of data
exceeded) during
inline code
generation.
Data type of the I/O
module(s) is not
supported
Unknown module
type of the flash
program memory
Error occurred while
writing to the flash
memory
Error occurred while
erasing a flash sector
The I/O module
configuration after an
internal data bus
reset differs from the
one after the last
controller startup.
Remedy
-
Switch off the power to the controller
and replace it.
-
Then switch the power back on.
-
Switch off the power to the
controller.
-
Reduce the number of I/O modules.
-
Switch the power back on.
-
Update the controller firmware. If this
error persists, there is an error in the
I/O module. Identify the error as
follows:
-
Switch off the power supply.
-
Place the end module in the middle
of the I/O modules connected to the
system.
-
Switch the power back on.
-
If the I/O flashes red switch off the
power supply again and place the
end module in the middle of the first
half of the I/O modules (toward the
controller).
-
If the LED is no longer flashing,
switch off the power supply and
place the end module in the middle
of the second half of the I/O modules
(away from the controller).
-
Switch the power back on.
-
Repeat this procedure until you
establish which I/O module is
defective. Then replace that module.
-
Switch off the power to the controller
and replace it.
-
Then switch the power back on.
-
Switch off the power to the controller
and replace it.
-
Then switch the power back on.
-
Restart the controller by first
switching off the power supply and
then switching it back on, or
by pressing the Reset button on the
controller.
Diagnostics 331