750-482/000-001 2AI 4-20mA HART NAMUR NE43
9.1.2

Startup on the 75x-xxx via PLC Library

This section describes the most important steps for commissioning the HART I/O
module on a 75x-xxx fieldbus coupler/controller using the HART library.
In addition to the fully installed and connected hardware of the fieldbus node with
fieldbus coupler/controller interface, it is necessary to install the following
software before carrying out the operation described.

Table 38: Required Software for Startup on 75x-xxx via PLC Library

No. Software name
1
WAGO-I/O-CHECK
(optional)
2
WAGO-I/O-PRO CAA
3
WagoLibHART_0x.lib
When the HART I/O module is delivered, the default operating mode (2 AI + 6-
byte mailbox) is preset.
If the operating mode has already been changed, e.g., the module has been
used in a PROFIBUS system, the operating mode must be parameterized again
for the default setting
1.
Launch WAGO-I/O-CHECK and set the operating mode to "2 AI + 6-byte
mailbox".
Proceed as described in the Section "Operating Modes" > ... > "Setting via
WAGO-I/O-CHECK".
WAGO-I/O-CHECK up to Version 3.17.1.17:
Setting Limitations for PROFIBUS Operating Modes
For the PROFIBUS operating modes "1, 2, 3 or 4 HART variable(s) per channel",
switching via WAGO-I/O-CHECK and operation on a fieldbus coupler other than
a PROFIBUS fieldbus coupler (750-333) or controller (750-833) is not currently
possible. A HART I/O module set up for HARD dynamic variables using GSD
files can therefore currently only be operated with a PROFIBUS fieldbus coupler
(750-333) or controller (750-833).
It is then possible to restore the default state of the HART I/O module using
WAGO-I/O-CHECK and the PROFIBUS fieldbus coupler (750 333) or controller
(750-833). Make sure that the PROFIBUS fieldbus coupler (750-333) or
controller (750-833) is not parameterized using GSD files.
Launch WAGO-I/O-PRO CAA, select the Resources tab and double-click
2.
in the tree structure on Library Manager to open the respective dialog.
Integrate the "WagoLibHART_0x.lib" library for your "IEC 61131-3" project.
Description
Commissioning tool for the
WAGO-I/O-SYSTEM 750
Programming tool IEC
61131-3; CAA Version
2.3; CODESYS
Automation Alliance
WAGO-I/O-PRO Libraries Download:
Commissioning