12.2.4
Meaning of Blink Codes and Procedures for
Troubleshooting
This section describes the diagnostics presented as blink codes via the MS
LEDs.
If the diagnostics cannot be cleared by the measured specified for them, contact
WAGO support. Be ready to explain to them the blink code that is displayed.
Phone:
Fax:
E-mail:

Table 240: Overview of MS-LED Error Codes

Error Code
1

Table 241: Error Code 1, Explanation of Blink Codes and Procedures for Troubleshooting

Error
Argument
5
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
+49 571 887 555
+49 571 887 8555
support@wago.com
Explanation
Configuration error
Cause
Error when
synchronizing the
controller
configuration with the
internal data bus
Remedy
-
Check the information of the
connected I/O modules in the
CODESYS controller configuration.
-
Adjust this to match the I/O module
that is actually inserted.
-
Recompile the project.
-
Reload the project into the controller.