3.3.2

Power Jumper Contacts/Field Supply

Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury.
The controller 750-8207is equipped with 3 self-cleaning power contacts for
transferring of the field-side power supply to down-circuit I/O modules. These
contacts are designed as spring contacts.

Figure 4: Power Jumper Contacts

Table 5: Legend for Figure "Power Jumper Contacts"

Contact
1
2
3
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded.
If exceeded, insert an additional supply module.
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
Type
Spring contact
Spring contact
Spring contact
Device Description
Function
Potential transmission (U
for field supply
Potential transmission (0 V)
for field supply
Potential transmission (ground)
for field supply
31
)
V
Manual