Mounting; Installation Position; Overall Configuration - WAGO 750-8207 Manual

Pfc200 cs 2eth rs 3g plc - controller pfc200
Table of Contents

Advertisement

72

Mounting

5
Mounting
5.1

Installation Position

Along with horizontal and vertical installation, all other installation positions are
allowed.
Use an end stop in the case of vertical mounting!
In the case of vertical assembly, an end stop has to be mounted as an additional
safeguard against slipping.
WAGO order no. 249-116
WAGO order no. 249-117
5.2

Overall Configuration

The maximum total length of a fieldbus node without fieldbus coupler/controller is
780 mm including end module. The width of the end module is 12 mm. When
assembled, the I/O modules have a maximum length of 768 mm.
Examples:
64 I/O modules with a 12 mm width can be connected to a fieldbus
coupler/controller.
32 I/O modules with a 24 mm width can be connected to a fieldbus
coupler/controller.
Exception:
The number of connected I/O modules also depends on the type of fieldbus
coupler/controller is used. For example, the maximum number of stackable I/O
modules on one PROFIBUS DP/V1 fieldbus coupler/controller is 63 with no
passive I/O modules and end module.
Observe maximum total length of a fieldbus node!
The maximum total length of a fieldbus node without fieldbus coupler/controller
and without using a 750-628 I/O Module (coupler module for internal data bus
extension) may not exceed 780 mm.
Also note the limitations of individual fieldbus couplers/controllers.
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
750-8207 PFC200 CS 2ETH RS 3G
End stop for DIN 35 rail, 6 mm wide
End stop for DIN 35 rail, 10 mm wide