Plc Side Setting (Cp-9200Sh Series, Cp-312, Cp-317 Series) - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

6.3.4
PLC side setting (CP-9200SH
series, CP-312, CP-317
series)
POINT
POINT
POINT
YASKAWA PLC
For details of YASKAWA PLCs, refer to the following
manuals.
YASKAWA PLC user's Manual
Parameter settings
Make the parameter settings with a peripheral tool.
(1) Settings for CP-218IF
Item
Module Type
CPU Number
Circuit Number
Hot Swapping
Item
CNO 03
Local Port
10500
Node IP
192.168.001.018
*1
Address
Node
05016
*1
Port
Connection
TCP
Type
Protocol
Extended
Type
MEMOBUS
Code
BIN
*1
Be sure to set the values above for the address so that the
GOT communicates with the programmable controller
correctly.
For the Host Address setting on the GOT side, refer to the
following.
6.3.2 ■ Ethernet setting
(2) Settings for CP-218IF
Item
IP Address
Transmission
Response Time
parameter
Count of Retry
setting
(Number of Retries)
Connection Number
Local Port
Node IP Address
Connection
Node Port
parameter
Connection Type
setting
Protocol Type
Code
Node Name
6 - 28
6. CONNECTION TO YASKAWA PLC
6.3 Ethernet Connection
Set value
CP-218
01
01
CNO 04
CNO 05
10501
10030
192.168.001.020
192.168.001.073
05017
21001
TCP
UDP
Extended
Extended
MEMOBUS
MEMOBUS
BIN
BIN
Set value
IP address for 218TXB
Not required
Not required
1
10500
Local IP address of GOT
Local port No. of GOT
UDP
Extended MEMOBUS
BIN
Any string
Settings by DIP switch
(1) Settings for 218TXB
Set the DIP switch (SW2) as follows.
ON
Setting Item
Set value
N/O
Mode Selection
*1
Not used
-
Transmission
10/100
Speed
Transmission
F/H
Mode
INIT
Initial Startup
*2
Test
TEST
*1
Turn off all the unused switches.
When even one of those switches is on, the PLC may not
normally operate.
*2
When the PLC is started with the TEST switch on, the
module starts the self-diagnosis and may not perform the
communication.
Turn off the switch before the communication is started.
N/O
-
10/100
F/H
-
-
INIT
TEST
OFF
Setting range
ON: Extended mode (13
channels, up to 1024 words)
ON
OFF: Basic mode (10 channels,
up to 512 words)
OFF
-
ON :10Mbps
OFF
OFF :100Mbps
ON: Full duplex mode
OFF
OFF: Half duplex mode
ON: Start up by the default IP
address and the engineering port
No.
OFF
OFF: Start up by the IP address
and the engineering port No. set
for CP-717
ON: The module starts the self-
diagnosis when the PLC is
started.
OFF
OFF: The module does not start
the self-diagnosis when the PLC
is started.