Plc Side Setting (Cp-9200Sh Series, Cp-312, Cp-317 Series) - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(2) SIEMENS S7-200
Item
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 19200bps)
Set this item when change the data
length used for communication with
Data Bit
the connected equipment.
(Default: 8bits)
Specify the stop bit length for
Stop Bit
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
Parity
during communication.
(Default: Even)
Specify the adapter address (station
No. of the adapter to which the GOT
Adapter Address
is connected) in the connected
network.
(Default: 0)
Specify the host address (station No.
of the PLC that the GOT will monitor)
Host Address
in the connected network.
(Default: 2)
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
15 - 8
15. CONNECTION TO SIEMENS PLC
15.2 Serial Connection
Description
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 31
1 to 31
15.2.5 PLC Side Setting
POINT
POINT
POINT
SIEMENS PLC
For details of SIEMENS PLCs, refer to the following
manuals.
SIEMENS PLC user's Manual
Model name
PLC CPU
S7-200
HMI Adapter
6ES7 972-0CA11-0XA0
6ES7 901-3BF20-0XA0
PC/PPI cable
6ES7 901-3CB30-0XA0
15.2.6 Connecting to HMI Adapter
Communication settings
The following communication settings are made at the
communication detail settings of the GOT side.
For details, refer to the following.
15.2.4 Communication detail settings
Setting item
Transmission speed
Data bit
Parity bit
Stop bit
Adapter address
Host address
Refer to
15.2.7
15.2.6
15.2.7
PLC side setting
9600bps, 19200bps, 38400bps
8bits (fixed)
Odd (fixed)
1bit (fixed)
1 to 31
1 to 31