7.11.2 Auxiliary Axis MCP Alarms (Yxxx)
Y02 AUX SYSTEM ALM
Error No.
0050
0051
Y03 AUX AMP UNEQU.
Error No.
Axis No.
Downloaded from
ManualsNet.com
7.11 Auxiliary Axis Alarms
An error occurred in the data transmitted between the MCP and
drive unit after the power was turned on.
Details
Background error
0000
CRC error
(10 times/910.2ms)
0001
CRC error (2 continuous times)
0002
Reception timing error
(2 continuous times)
××03
Data ID error
(2 continuous times)
××: Axis No.
××04
No. of reception frames error
(2 continuous times)
××: Axis No.
The drive unit is not correctly connected.
Check the auxiliary axis drive unit mounting state.
• Check the end of the cable wiring.
• Check the cable for broken wires.
• Check the connector insertion.
The auxiliary axis drive unit input power is not being input.
The auxiliary axis drive unit axis No. switch is illegal.
bit correspondence (bit 0 : 1st axis, bit 1: 2nd axis, bit 2: 3rd axis, ...bit6: 7th axis)
(Note) As for C6 system, up to 5 axes of MR-J2-CT can be connected.
Thus, the setting range is bit 0 to 4
search engine
7. List of Alarms
The software or hardware may be
damaged.
Contact the service center.
A communication error has occurred
between the controller and drive unit.
• Take measures against noise.
• Check that the communication cable
connector between the controller and
drive unit and one between the drive units
are tight.
• Check whether the communication cable
between the controller and drive unit and
one between the drive units are
disconnected.
• A driving amplifier may be faulty. Take a
note of the 7-segment LED contents of
each drive unit and report to the Service
Center.
Details
IV - 88
Remedy