Troubleshooting

20.2.8 In Case of Communication Error (RS-232C)

 Object
Product no.
Communication Interface
Control unit
standard
RS-232C (3-wire) × 1 channel
configuration
AFPX-COM1
RS-232C (5-wire) × 1 channel
AFPX-COM2
RS-232C (3-wire) × 2 channel
AFPX-COM4
RS-232C (3-wire) × 1 channel
AFPX-COM5
RS-232C (3-wire) × 1 channel
 Situation
Connections and settings may be incorrect.
PROCEDURE
1. Confirm the setting of the system register.
Verify if the setting corresponding to the communication port number assigned is
correct. When selecting the inter-PLC link, verify if the connection area is
repeated.
2. Verify if the CS signal is ON.
When using 3-wire type, set the connection RS signal and CS signal to ON. When
using 5-wire type, verify the RS signals of the communication cassette LED and
the matched devices.
3. Verify the connection with the matched devices.
Confirm that the SD terminal of the matched device is connected to the RD
terminal at the PLC side, and the RD terminal of the matched device is connected
to the SD terminal at the PLC side. Also, make sure the SG terminals from both
devices are connected.
20-10
Communication Port No. Assigned
Main
Cassette
Unit
mounting part 1
COM0
COM1
COM2
Cassette
mounting part 2
COM3
COM4