26.1.2 Performance Specifications

Item
No. of control I/O points
Program mode / Control
method
Program memory
Comments storage
Basic
instructions
No. of
instructions
High-level
instructions
Program capacity
Operation processing speed
IO refresh
+ base time
External input (X)
External output (Y)
Internal relay (R)
Special internal relay
(R)
Timer, counter
(T / C)
Link relay (L)
Data register (DT)
Link data register
(LD)
Index register (I)
Differential points (DF, DF /,
DFI)
Master control relay points
No. of labels (JMP+LOOP)
No. of step ladders
No. of subroutines
(Note 1): When changing the system register No.0 (sequence program capacity setting), the data register (DT)
capacity will also change.
(Note 2): Refresh time of FP0 expansion unit: No. of 8-point units used x 0.8 msec, No. of 16-point units:used × 1.0
msec, No. of 32-point units used × 1.3 msec, No. of 64-point units used × 1.9 msec
(Note 3): The number of points in the above table is the number of points of operation memory.. The actual number of
points for input and output is determined by the combination of hardware.
(Note 4): The number of timer points can be changed by the setting of the system register no. 5. Points can be
increased with the auxiliary timer.
Specifications
General-purpose I/O part of the cotnrol unit: 16 points (DCinput: 8 points /
Transistor output: 8 points)
For E16 expansion I/O unit: up to 32 points
For E30 expansion I/O unit: up to 256 points (up to 8 expansion units)
For FP0R expansion I/O unit: up to 112 points (up to 3 expansion units)
Relay symbol / cyclic operation mode
Built-in Flash-ROM (requires no backup battery)
Saved programs, system registers, position control data and position control data.
All comments including I/O comments, explanatory notes, interlinear comments
can be stored. (Backup battery is not necessary: 1M bytes)
Approx. 120
Approx. 230
24k / 32k / 40k step (Note 1)
Up to 7k steps: basic instruction 0.04 µs - / step, high-level instruction 0.22 µs - /
step
Above 7k steps: basic instruction 0.7 µs - / step, high-level instruction 1.73 µs - /
step
Single control unit: below .0.12µs
For expansion unit E16: 0.34 ms × No. of units
For expansion unit E30: 0.47ms × No. of units
For expanded FP0 adapter: 1.4ms + FP0 expansion unit refresh time (note 2)
2272 points (X0-X141F) (Note 3)
2272 points (Y0-Y141F) Not 3)
8192 points (R0-R511F)
240 points
1024 points (note 4)
(Initial setting Timer 1008 points: T0-T1007, counter 16 points: C1008-C1023)
Timer measurable up to (1msec/10msec/100msec/1sec units) x 32767
Counter measures 1-32767
2048 points (L0 - L127F)
64k, 32k, 12k words (Note 1)
256 words (LD0 - LD255)
14 words (I0 - ID)
Program capacity
256 points
256 points
1000 steps
500 subroutines