Panasonic FP-XH M8N16PD User Manual page 488

Programmable controller
Table of Contents

Advertisement

Specifications
 Pulse input setting area
Offset
Name
address
Pulse input
H3A0
mode of CH1
Pulse input
H3A1
mode of CH2
Pulse input
H3A2
mode of CH3
Pulse input
H3A3
mode of CH4
26-32
Default Setting range and description
Set the pulse input function.
bit
Name
Rotation
0
direction
1
Pulse input
3-2
mode
Input
5-4
transfer
multiple
H20
Pulse input
7-6
purpose
Pulse input
10-8
time
constant
15-11
H20
H20
Refer to the description for the axis 1
H20
Description
Set the rotation direction of pulse input.
0: Forward
1: Reverse
Set the input method of pulse input.
Bit3 Bit2
0
0: 2-phase input
0
1: Direction distinction input
1
0: Individual input
1
1: Reserved for system (When set, it will be 2-
phase input.)
Set the multiple when setting the pulse input mode
(Bit2-3) to "2-phase input".
Bit5 Bit4
0
0: x1 (1 multiple))
0
1: x2 (2 multiple)
1
0: x4 (4 multiple)
1
1: Reserved for system (When set, it will be 4
multiple.)
Specify the purpose of pulse input for each axis.
・Pulsar: Connect a manual pulsar to the pulse input.
・High-speed counter
Bit7 Bit6
0
0: Pulsar
0
1: Reserved for system (When set, it will be
pulsar.)
1
0: High-speed counter
1
1: Reserved for system (When set, it will be
pulsar.)
Set the time constant of each pulse input signal.The
pulse inputs A and B of the same axis are the same
input time constant.。
Bit10 Bit9 Bit8
0
0
0 :No input time constant
0
0
1: 0.1 µs
0
1
0: 0.5 µs
0
1
1: 1.0 µs
1
0
0: 2.0 µs
1
0
1: 10.0 µs
1
1
0: No input time constant
1
1
1: No input time constant

Advertisement