Auxiliary Function
 Current value update area (positioning memory: common area)
Memory
address
Name
(Hex)
Current value update
HC0
request flag
Current value update
HC8-HC9
coordinate of axis 1
Current value update
HCA-HCB
coordinate of axis 2
Current value update
HCC-HCD
coordinate of axis 3
Current value update
HCE-HCF
coordinate of axis 4
Current value update
HD0- HD1
coordinate of axis 5
Current value update
HD2- HD3
coordinate of axis 6
Current value update
HD4- HD5
coordinate of (virtual)
axis 7
Current value update
HD6-HD7
coordinate of (virtual)
axis 8
(Note): The current value update request flag is designated via the H constant. For update request of axis-1 and axis-
2, write H3.
KEY POINTS
The current value changed via current value update is the current value
after conversion of unit system.
17-10
Description
Change the current value coordinates after conversion of unit system
managed by the unit controller (offset addresses H3E-H3F of the axes)
into the values set in the current value updated coordinates areas
(HC8-HD7) only when the bit corresponding to the axes turns from 0 to
1.
Upon completion of the change, the unit controller will automatically
clear the corresponding bit of the current value update request flag
area (HC0).
bit
Name
Current value update
0
request of axis 1
Current value update
1
request of axis 2
Current value update
2
request of axis 3
Current value update
3
request of axis 4
Current value update
4
request of axis 5
Current value update
5
request of axis 6
Current value update
6
request of (virtual)
axis 7
Current value update
7
request of (virtual)
axis 8
15-8
Saves the preset coordinates as the current value.
Initial
Description
value
0: unchanged
0
1: Coordinate origin of
corresponding content
0
changed
(Auto clearing by the unit
0
controller after execution)
0
0
0
0