Register
Number
Add-on cassette verify
DT90011
mismatched unit position
DT90012
Unused
-DT90013
Operation auxiliary register
DT90014
of the data shift
instruction
DT90015
Operation auxiliary register
of the division instruction
DT90016
Operation error address
DT90017
(hold)
Operation error address
DT90018
(latest)
DT90019
2.5 ms RING counter
DT90020
10 µs RING counter
DT90021
Unused
Scanning time (current
DT90022
(note
value)
DT90023
Scanning time (min)
DT90024
Scanning time (max)
(Note 1): The scanning time and operation cycle time only display in RUN mode. The scanning time of the operation
is not displayed in PROG. mode. When the maximum and minimum value are shifted between RUN mode and
PROG. mode, they are temporarily cleared.
(Note 2): During one scan, it is updated once at the beginning.
(Note 3): DT90020 is also updated when executing F0 (MV), therefor, it can be used to measure the time interval.
Name
When the FP-X add-on cassette installation state
turns to power ON, the corresponding bit to the add-
on cassette number is ON (1). Monitor with BIN
display.
15
ON(1):Abnormal OFF(0):Normal
After executing the data shift instruction F105 (BSR)
or F106 (BSL), the 1 digit data removed out is saved
to the bit 0 - 3.
Execute F0 (MV) instruction, values can be read and
write.
When executing 16-bit division instruction F32 (%),
F52 (B%), the 16 bit of the remainder is saved to
DT90015.
When executing 32-bit division instruction F33 (D%),
F53 (DB%), the 32 bit of the remainder is saved to
DT90015-DT90016. Execute F1 (DMV) instruction,
values can be read and write.
After running, the address occurs an operation error
first is stored. Please use decimalism display to
perform monitoring.
The address where an error occurred is stored.
Update when each time an error occurs. Please use
decimalism display to perform monitoring.
The stored value is increased by 1 every 2.5 ms. (H0-
HFFFF)
2
(Note
)
The difference between 2 points (absolute value) ×
2.5 ms = elapsed time between 2 points
Saved value +1 every 10.00 µs. (H0-HFFFF)
The difference between 2 points (absolute value) ×
2
3
(note
.
)
10.00 µs=(elapsed time between 2 points)
note) the correct value is 10.00 µs.
The current value of the scanning time is saved.
[Saved value (decimal)] × 0.1 ms
1
)
(Example) For K50, it indicates within 5 ms.
The minimum value of the scanning time is saved.
1
(note
)
[Saved value (decimal)] × 0.1 ms
(Example) For K50, it indicates within 5 ms.
The maximum value of the scanning time is saved.
1
(note
)
[Saved value (decimal)] × 0.1 ms
(Example) For K125, it indicates within 12.5 ms.
26.7 Table of Special Data Registers
Description
11
7
3 2 1 0 (Bit No.)
2 1 (Expansion No.)
R
W
×
×
×
×
×
×
×
×
×
×
×
×
26-79